ACCESSORY KIT INSTALLATION INSTRUCTIONS
1NP0347 / 1NP0348 / 1NP0349
PROPANE CONVERSION ACCESSORY - INDUCED COMBUSTION FURNACES
MODELS - P*HU/P*DN/P*UR/P*DH/FL8/G9T-UP/G9T-DH/FG9-UP/
FG9-DH/G8T-UH/L8T-UH/G8T-DN/L8T-DN/GF9/GM9/GY9/XYF80/XYF90
035-14445-000 Rev. F (0404)
GENERAL
This kit is intended for the conversion of new equipment only,
from natural gas to propane gas operation.
All unit installations above 2,000 ft. must be field
derated as required by the National Fuel Gas Code, ANSI
Z223.1 (latest edition), or in Canada, CAN/CGA B149.1 or .2
and all other applicable local codes and utility requirements.
This instruction covers the conversion of this unit when it is
equipped with a White-Rodgers gas valve. The installation
instruction supplied with the unit is to be used for all other
aspects of the installation.
This conversion kit is to be installed by a qualified service agency in accordance with the manufacturer’s instructions
and all applicable codes and requirements of the authority having jurisdiction. If the information in these instructions
are not followed exactly, a fire, an explosion or production of carbon monoxide may result causing property damage,
personal injury or loss of life. The qualified service agency is responsible for the proper installation of this kit. The
installation is not proper and complete until the operation of the converted appliance is checked as specified in the
manufacturer’s instructions supplied with the kit.
The conversion of new certified central heating gas appliances must conform to directions outlined in this instruction.
Installation must be made in accordance with American National Standard National Fuel Gas Code, ANSI Z223.1-lat-
est edition, unless superseded by local codes. For Canadian installations, the conversion shall be carried out in accor-
dance with the requirements of the Provincial authorities having jurisdiction and in accordance with the CAN1-B149.1
and .2 installation codes.
The manufacturer accepts no responsibility for malfunctions due to improper conversions
Lo-NOx furnaces requiring propane (LP) gas must have the NOx screens removed prior to operation. Failure to do so may
result in operational problems and/or reduced heat exchanger life. Follow the instructions below for removal of the NOx
screens.
PROPANE CONVERSION KIT APPLICATION
MODELS USAGE (INPUTS) ACCESSORY
P*HU/P*DN/FL8
G8T-UH/L8T-UH/
G8T-DN/L8T-DN/XYF80
40, 80, & 100 MBH Only
1NP0347
P*HU/P*DN/FL8
G8T-UH/L8T-UH/
G8T-DN/L8T-DN/XYF80
60, 115 & 130 MBH Only
1NP0348
P*HU 160 MBH Only 1NP0349
P*UR/P*DH
G9T-UP/FG9-UP
G9T-DH/FG9-DH
40 - 120 MBH Only 1NP0347
P*UR/G9T-UP/FG9-UP 140 MBH Only
1NP0349
GF9/GM9/GY9/XYF90 All Models 1NP0347
Improper installation, adjustment, service or mainte-
nance can cause injury or property damage; there-
fore, only a qualified installer or qualified service
personnel should perform this conversion.
CONTENTS OF KIT
Parts Common to All Kits:
DESCRIPTION PART NUMBER QTY
Gas Valve Conversion Kit,
White-Rodgers . 025-25463-000 1
(WR #92-0923)
Propane Conver. Label 035-11635-000 1
Kit Installation Instruction 035-14445-000 1
1NP0347 Kit:
Main Burner Orifices #55 . 029-20423-055 7
1NP0348 Kit:
Main Burner Orifices #56 . 029-20423-056 7
1NP0349 Kit:
Main Burner Orifices #54 . 029-20423-054 7
Vedere la pagina 0
1 2 3 4

Sommario

Pagina 1 - 1NP0347 / 1NP0348 / 1NP0349

Unitary Products GroupACCESSORY KIT INSTALLATION INSTRUCTIONS1NP0347 / 1NP0348 / 1NP0349PROPANE CONVERSION ACCESSORY - INDUCED COMBUSTION FURNACESMODE

Pagina 2 - (Lo-NOx Models Only)

035-14445-000 Rev. F (0404)2 Unitary Products GroupFURNACE CONVERSION1. Remove the upper access door. On 90+AFUE units,remove the burner box cover.2.

Pagina 3 - TESTS AND ADJUSTMENTS

035-14445-000 Rev. F (0404)Unitary Products Group 36. Remove the screws holding the burner assembly to thevestibule panel. It may be necessary to remo

Pagina 4

Subject to change without notice. Printed in U.S.A. 035-14445-000 Rev. F (0404)Copyright © by York International Corp. 2004. All rights reserved. Supe